High Profile Trim

Common details and conditions related to situations requiring Chief's high profile trim.

High Profile Trim Sections & Details

All details downloadable in .dwg and .pdf

Table of Contents

STC-MSC Roof - High Profile Trim - Eave STC-MSC Low Side w High Profile Eave Gutter STC-MSC Low Side w High Profile Eave Gutter and No Wall Panel STC-MSC High Side w High Profile Eave Trim STC-MSC High Side w High Profile Eave Trim and Thermal Spacer STC-MSC Roof - High Profile Trim - Gable

STC-MSC Gable Lead w High Profile Trim and Thermal Spacer STC-MSC Gable Tail w High Profile Trim and Thermal Spacer STC-MSC Gable Tail w High Profile Trim-Termination Trim and Thermal Spacer STC-MSC Gable End w High Profile Gable Trim-Field Bend Vertical Leg and Thermal Spacer STC-MSC Gable End w High Profile Gable Trim-Field Bend Vertical Leg-Term Trim and Thermal Spacer STC-MSC Roof - High Profile Trim - Eave Extension STC-MSC High Side Eave Ext w Low Floating Eave High Profile Eave Trim and CS-AP Soffit STC-MSC High Side Eave Ext w Low Floating Eave High Profile Eave Trim and NO Soffit STC-MSC Roof - High Profile Trim - Gable Extension STC-MSC Gable Ext Lead End High Profile Trim-AP Soffit and Thermal Spacer STC-MSC Gable Ext Lead End High Profile Trim-CS Soffit and Thermal Spacer STC-MSC Gable Ext Lead End High Profile Trim-NO Soffit and Thermal Spacer STC-MSC Gable Ext Only at High Side High Profile Eave Trim NO Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg NO Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim AP Sof and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim CS Soffit Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim NO Sof and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-NO Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Term Trim AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Term Trim CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End High Profile Trim-Term Trim NO Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w High Profile Eave Gutter and CS-AP Soffit STC-MSC Low Side Eave Ext w High Profile Eave Gutter and NO Soffit

MVF-MVP Roof - High Profile Trim - Eave MVF-MVP Low Side w High Profile Eave Gutter MVF-MVP Low Side w High Profile Eave Gutter and No Wall Panel MVF-MVP High Side w High Profile Eave Trim MVF-MVP High Side w High Profile Eave Trim and Thermal Spacer MVF-MVP Roof - High Profile Trim - Gable MVF-MVP Gable Lead End w High Profile Trim and Thermal Spacer

Table of Contents

MVF-MVP Gable Tail End w High Profile Trim and Thermal Spacer MVF-MVP Gable Lead End w Field Cut Roof Panel - High Profile Trim and Thermal Spacer MVF-MVP Roof - High Profile Trim - Eave Extension MVF-MVP Eave Ext at Low Side w High Profile Eave Gutter and CS-AP Soffit MVF-MVP Eave Ext at Low Side w High Profile Eave Gutter and NO Soffit MVF-MVP Eave Ext at High Side w High Profile Eave Trim and CS-AP Soffit MVF-MVP Eave Ext at High Side w High Profile Eave Trim and NO Soffit MVF-MVP Roof - High Profile Trim - Gable Extension MVF-MVP Gable Ext Lead End w High Profile Trim-AP Soffit and Thermal Spacer MVF-MVP Gable Ext Lead End w High Profile Trim-CS Soffit and Thermal Spacer MVF-MVP Gable Ext Lead End w High Profile Trim-NO Soffit and Thermal Spacer MVF-MVP Gable Ext Only at High Side Eave Strut NO Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w High Profile Trim-AP Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w High Profile Trim-CS Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w High Profile Trim-NO Soffit and Thermal Spacer

STC-MSC Roof - High Profile Trim - Eave

STC-MSC Roof High Profile Trim Eave

STC-MSC Low Side w High Profile Eave Gutter

1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS

BL

#12-14 X 1 1/4" (6" C.C for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C) TRIM CAP (TCM) EAVE GUTTER (EGMH) 1/4-14 X 7/8" WT (6" C.C.) GUTTER STRAP (GSMH) AT EACH PANEL HI-RIB #12-14 X 1 1/4" (TRIM COLOR) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) *TRAPEZOID PLUG (TRP) EACH HIGH RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM)

**(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

4 1 2 "

STC/MSC ROOF PANEL 1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system. ** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. * See isometric Trapezoid Plug Installation detail for installation instructions.

EAVE STRUT INSIDE CLOSURE ***

WALL PANEL

STC-MSC Low Side w High Profile Eave Gutter and No Wall Panel

1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)

**(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

* TRAPEZOID PLUG (TRP) EACH HIGH RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM)

BL

STC/MSC ROOF PANEL 1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS

DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM)

3 3 8 "

#12-14 X 1 1/4" (TRIM COLOR)

#12-14 X 1 1/4" (12" C.C.) SPECIAL TRIM (SPT- ) EAVE GUTTER (EGMH) *** GUTTER STRAP (GSMH) AT EACH PANEL HI-RIB 1/4-14 X 7/8" WT (6" C.C.)

EAVE STRUT

** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. * See isometric Trapezoid Plug Installation detail for installation instructions.

DRAFTING NOTES: *** Trim cap to cover web depth.

STC-MSC High Side w High Profile Eave Trim

TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) PRE-GLUED THERMAL SPACER **** (NOT BY CHIEF)

1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE

BL

1/4-14 X 7/8" (12" C.C.) HI-SIDE EAVE TRIM (HETMH) BACK-UP PLATE **TRI-BEAD TAPE MASTIC

2 3

4 "

STC/MSC ROOF PANEL

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system. **** Thermal spacer to be used with no insulation.

1/4-14 X 7/8" (12" C.C.) OUTSIDE CLOSURE

JAMB TRIM

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

* For screw spacing refer to High Eave Trim detail in the MSC/STC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.

INSIDE CLOSURE ***

EAVE STRUT WALL PANEL

STC-MSC High Side w High Profile Eave Trim and Thermal Spacer

TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)

BL

1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE

2 3

THERMAL SPACER (NOT BY CHIEF)

4 "

BACK-UP PLATE **TRI-BEAD TAPE MASTIC

STC/MSC ROOF PANEL

OUTSIDE CLOSURE

1/4-14 X 7/8" (12" C.C.) HI-SIDE EAVE TRIM (HETMH) 1/4-14 X 7/8" (12" C.C.)

JAMB TRIM

INSIDE CLOSURE ***

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

EAVE STRUT WALL PANEL

* For screw spacing refer to High Eave Trim detail in the MSC/STC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system.

STC-MSC Roof - High Profile Trim - Gable

STC-MSC Roof High Profile Trim Gable

STC-MSC Gable Lead w High Profile Trim and Thermal Spacer

GABLE TRIM (GTMH) RAKE SUPPORT (A-20-T) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

TRI-BEADTAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.)* STC/MSC ROOF PANEL THERMAL SPACER

1

BL

***

INSIDE CLOSURE

(NOT BY CHIEF)

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) WALL PANEL ** OUTSIDE CLOSURE

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN

* It is important that 1/4-14 x 1 1/4" shoulders are installed through the center of the slotted holes of the rake support.

** NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Gable Tail w High Profile Trim and Thermal Spacer

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH)

TRI-BEADTAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) STC/MSC ROOF PANEL THERMAL SPACER

1

BL

(NOT BY CHIEF)

***

INSIDE CLOSURE

PURLIN

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(2) 1/4-14 X 7/8"

** OUTSIDE CLOSURE WALL PANEL 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

* It is important that 1/4-14 x 1 1/4" shoulders are installed through the center of the slotted holes of the rake support.

** NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Gable Tail w High Profile Trim-Termination Trim and Thermal Spacer

TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE MASTIC GABLE TRIM (GTMH) RAKE SUPPORT (A-20-T) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

* 1/4-14 X 1 1/4" SHOULDER (24" C.C.) 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP) TRI-BEAD TAPE MASTIC PANEL CLIP W/FASTENERS (REFER TO ROOF PANEL PLAN)

BL

STC/MSC ROOF PANEL

(NOT BY CHIEF)

THERMAL SPACER

INSIDE CLOSURE ***

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) WALL PANEL **OUTSIDE CLOSURE

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN

** Field cut outside closure for higher roof pitches. * It is important that 1/4-14 x 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system.

STC-MSC Gable End w High Profile Gable Trim-Field Bend Vertical Leg and Thermal Spacer

GABLE TRIM (GTMH)

1

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) RAKE SUPPORT (A-20-T)

BL

* 1/4-14 X 1 1/4" SHOULDER (24" C.C.) STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) THERMAL SPACER (NOT BY CHIEF)

***

INSIDE CLOSURE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(2) 1/4-14 X 7/8"

WALL PANEL **OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN

* It is important that 1/4-14 x 1 1/4" shoulders are installed through the center of the slotted holes of the rake support.

** NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Gable End w High Profile Gable Trim-Field Bend Vertical Leg-Term Trim and Thermal Spacer

TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE SEALER GABLE TRIM (GTMH) RAKE SUPPORT (A-20-T)

* 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) 1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-T) TRI-BEAD TAPE SEALER STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)

1

BL

THERMAL SPACER

(NOT BY CHIEF)

RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

PURLIN

***

INSIDE CLOSURE

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM. * It is important that 1/4-14 x 1 1/4" shoulders are installed through the center of the slotted holes of the rake support.

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) ** OUTSIDE CLOSURE WALL PANEL

** NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Roof - High Profile Trim - Eave Extension

STC-MSC Roof High Profile Trim Eave Extension

STC-MSC Low Side Eave Ext w High Profile Eave Gutter and CS-AP Soffit

1/4-14 X 1 1/4" WT (8 PER PANEL)

1/4-14 X 7/8" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) * TRAPEZOID PLUG (TRP) AT EACH HIGH RIB GUTTER STRAP (GSMH) AT PANEL HI-RIBS #12-14 X 1 1/4" (TRIM COLOR) ** (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) STC/MSC ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

BL

1/4-14 X 1 1/4" WT (6 PER PANEL)

INSIDE CLOSURE ***

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE

EAVE GUTTER (EGMH)

EAVE EXTENSION FLASHING (EEFA)

EXTENSION FLASHING (EF) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.)

SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.) WALL PANEL

#12-14 X 1 1/4" (12" C.C.) 1/4-14 X 7/8" (12" C.C.) SOFFIT PANEL 1/4-14 X 1" (2 PER CLOSURE)

PANEL OVERHANG

GUTTER STRAP LAP

PITCH

9 8 3/4

<=3/4:12 >3/4:12 to <=1 1/2:12 >1 1/2:12 to <=2 1/2:12 >2 1/2:12 to <=3 1/2:12 >3 1/2:12 to <=4 1/2:12

5 5/8

5 11/16

5 11/16

8 1/2

** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. * See isometric Trapezoid Plug Installation detail for installation instructions.

5 13/16

8

5 15/16

7 9/16

All Dimensions in Inches DRAFTING NOTE: *** Inside closure must be provided on buildings with liner insulation system .

STC-MSC Low Side Eave Ext w High Profile Eave Gutter and NO Soffit

EAVE GUTTER (EGMH) GUTTER STRAP (GSMH) AT PANEL HI-RIBS 1/4-14 X 7/8" (12" C.C.) EAVE EXTENSION FLASHING (EEFA) EXTENSION FLASHING (EF) 1/4-14 X 7/8" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) * TRAPEZOID PLUG (TRP) AT EACH HIGH RIB #12-14 X 1 1/4" (TRIM COLOR) ** (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) STC/MSC ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT (8 PER PANEL)

TRAPEZOID PLUG (TRP) AT EACH HIGH RIB

BL

1/4-14 X 1 1/4" WT (6 PER PANEL) 1/8" X 3/8" BLIND RIVET (PARCHMENT) (2 PER PLUG)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

INSIDE CLOSURE ***

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

#12-14 X 1 1/4" (12" C.C.) 1/4-14 X 1" (2 PER CLOSURE)

PANEL OVERHANG

GUTTER STRAP LAP

PITCH

WALL PANEL

<=3/4:12 >3/4:12 to <=1 1/2:12 >1 1/2:12 to <=2 1/2:12 >2 1/2:12 to <=3 1/2:12 >3 1/2:12 to <=4 1/2:12

5 5/8

9 8 3/4

5 11/16

NOTE: Jamb trim around extension beam as required.

5 11/16

8 1/2

** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. * See isometric Trapezoid Plug Installation detail for installation instructions.

5 13/16

8

5 15/16

7 9/16

All Dimensions in Inches DRAFTING NOTE: *** Inside closure must be provided on buildings with liner insulation system .

STC-MSC High Side Eave Ext w Low Floating Eave High Profile Eave Trim and CS-AP Soffit

*1/4-14 X 7/8" WT TRI-BEAD TAPE MASTIC

1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE **TRI-BEAD TAPE MASTIC

3 1

2 "

BL

STC/MSC ROOF PANEL

BACK-UP PLATE

(NOT BY CHIEF) PRE-GLUED THERMAL SPACER

PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

HI-SIDE EAVE TRIM (HETMH) 1/4-14 X 7/8" (12" C.C.) HIGH SIDE EXTENSION FLASHING (HEEF)

(NOT BY CHIEF) PRE-GLUED THERMAL SPACER ****

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

*****

*****

HIGH PROFILE TRIM-UNSOFFITED HS EAVE EXT STC/ MSC

INSIDE CLOSURE ***

#12-14 X 1 1/4" (12" C.C.) 1/4-14 X 7/8" (12" C.C.) SOFFIT PANEL

TRIM TYPE HEEF HEHP

PURLIN SIZE

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE SOFFIT TRIM (ESTA) 1/4-14 X 7/8" (12" C.C.) WALL PANEL

8

10 HEEF = HIGHSIDE EAVE EXT. FLASHING HEHP = HIGHSIDE EAVE EXT. FLASHING DRAFTING NOTE: *** Inside closure must be provided on buildings with liner insulation system. **** Thermal spacer to be used with no insulation.

* For screw spacing refer to High Eave Trim detail in the MSC/STC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.

STC-MSC High Side Eave Ext w Low Floating Eave High Profile Eave Trim and NO Soffit

*1/4-14 X 7/8" WT TRI-BEAD TAPE MASTIC

STC/MSC ROOF PANEL TRAPEZOID PLUG (TRP) AT EACH HI-RIB PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER ****

1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE **TRI-BEAD TAPE MASTIC

3 1 2 "

BL

PRE-GLUED THERMAL SPACER

(NOT BY CHIEF)

BACK-UP PLATE

HI-SIDE EAVE TRIM (HETMH) 1/4-14 X 7/8" (12" C.C.) HIGH SIDE EXTENSION FLASHING (HEEF)

1/8" X 3/8" BLIND RIVET (PARCHMENT) (2 PER PLUG)

*****

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

HIGH PROFILE TRIM-UNSOFFITED HS EAVE EXT STC/ MSC

*****

INSIDE CLOSURE ***

TRIM TYPE HEEF HEHP

PURLIN SIZE

1/4-14 X 7/8" (12" C.C.)

8

10

NOTE: Jamb trim around extension beam as required * For screw spacing refer to High Eave Trim detail in the MSC/STC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.

PANEL CAP TRIM (SCT)

HEEF = HIGHSIDE EAVE EXT. FLASHING HEHP = HIGHSIDE EAVE EXT. FLASHING

WALL PANEL

DRAFTING NOTE: *** Inside closure must be provided on buildings with liner insulation system. **** Thermal spacer to be used with no insulation.

STC-MSC Roof - High Profile Trim - Gable Extension

STC-MSC Roof High Profile Trim Gable Extension

STC-MSC Gable Ext Lead End High Profile Trim-AP Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH)

BL

PURLIN CLOSURE (TYP.)

#12-14 X 1" PANCAKE HEAD EACH PURLIN #12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER

PANEL CLIP w/FASTENERS

PURLIN

PURLIN

STC/MSC ROOF PANEL

(2) 1/4-14 X 7/8"

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

THERMAL SPACER

(NOT BY CHIEF)

GABLE TRIM SUPPORT (GTS) (10'-0")

PURLIN CLOSURE (GPC)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

TOP VIEW

GABLE EXTENSION CHANNEL (GEC) EXTENSION GABLE FLASHING (EGFA) 1/4-14 X 7/8" (12" C.C.) **

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

AP SOFFIT PANEL

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR )

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

EAVE STRUT

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC/ MSC

JAMB TRIM (JT) INSIDE CLOSURE ***

TRIM TYPE EGFA EFHP

PURLIN SIZE

L OR H SYSTEM

8

HIGH HIGH

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PANEL SUPPORT TRIM (SSP) (TYP.) 1/4-14 X 7/8" (12" C.C.)

10

1/4 -14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Lead End High Profile Trim-CS Soffit and Thermal Spacer

1

PURLIN

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

1/4-14 X 7/8 (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH) (2) 1/4-14 X 7/8

STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS

PURLIN

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

THERMAL SPACER

(NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE (GPC)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EFCP)

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.) JAMB TRIM (JT) 1/4-14 X 7/8 (12" C.C.)

**

EAVE STRUT

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC/ MSC

L OR H SYSTEM

TRIM TYPE EFCP ECHP

PURLIN SIZE

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

INSIDE CLOSURE ***

8

HIGH HIGH

10

PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

EFCP = EXTENSION FLASHING HIGH PROFILE ECHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Lead End High Profile Trim-NO Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

1/4-14 X 1 1/4" WT (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER *1/4-14 X 1 1/4" SHOULDER (24" C.C.)

TRI-BEAD TAPE SEALER #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH) 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) (2) 1/4-14 X 7/8"

STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS

PURLIN

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN CLOSURE (GPC)

(2) #12-14 X 1 1/4"' PER CLOSURE

THERMAL SPACER

(NOT BY CHIEF)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

TOP VIEW

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

***

INSIDE CLOSURE

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

**

** HIGH PROFILE TRIM UNSOFFITED GABLE EXT STC/ MSC

TRIM TYPE

PURLIN SIZE

L OR H SYSTEM

WALL PANEL

EAVE STRUT

8

EF

HIGH HIGH

10

EFHP

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

EF- EXTENSION FLASHING EFHP - EXTENSION FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM

PURLIN CLOSURE INSTALLATION

STC-MSC Gable Ext Only at High Side High Profile Eave Trim NO Soffit and Thermal Spacer

1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE

BL

STC/MSC ROOF PANEL PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT

2 3

4 "

HI-SIDE EAVE TRIM (HETMH) 1/4-14 X 7/8" (12" C.C.) (TRIM COLOR BACK-UP PLATE **TRI-BEAD TAPE MASTIC

THERMAL SPACER (NOT BY CHIEF)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

EAVE SHIM TRIM (HSST1)

GABLE EXTENSION HIGH SIDE BOTTOM FLASHING (GEHB_)

EAVE STRUT

* For screw spacing refer to High Eave Trim detail in the MSC/STC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.

STC-MSC Gable Ext Tail End High Profile Trim-AP Soffit and Thermal Spacer

1

PURLIN

GABLE EXTENSION DIMENSION

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

1/4-14 X 1 1/4" WT (12" C.C.) TRI-BEAD TAPE SEALER #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH)

#12-14 X 1" PANCAKE HEAD EACH PURLIN #12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER *1/4-14 X 1 1/4" SHOULDER (24" C.C.)

STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS

PURLIN

PURLIN

THERMAL SPACER

(NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) 1/4-14 X 7/8"

PURLIN CLOSURE (GPC)

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

GABLE EXPANSION TRIM (GET)

TOP VIEW

GABLE EXTENSION CHANNEL (GEC) EXTENSION GABLE FLASHING (EGFA) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) ** 1/4-14 X 7/8" (12" C.C.)

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

AP SOFFIT PANEL

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

EAVE STRUT

INSIDE CLOSURE ***

PANEL SUPPORT TRIM (SSP)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC/ MSC

TRIM TYPE EGFA EFHP

PURLIN SIZE

L OR H SYSTEM

RAKE ANGLE (A-20-B)

1/4-14 X 7/8" (12" C.C.)

8

HIGH HIGH

JAMB TRIM (JT)

10

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Tail End High Profile Trim-CS Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH) 1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) ** EXTENSION FLASHING (EFCP) (2) 1/4-14 X 7/8"

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER *1/4-14 X 1 1/4" SHOULDER (24" C.C.)

STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS

PURLIN

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

THERMAL SPACER

(NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE (GPC)

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

EAVE STRUT

TRIM TYPE EFCP ECHP

L OR H SYSTEM

PURLIN SIZE

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC / MSC

***

INSIDE CLOSURE

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

8

HIGH HIGH

JAMB TRIM (JT)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

10

EFCP = EXTENSION FLASHING HIGH PROFILE ECHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg AP Soffit and Thermal Spacer

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

TRI-BEAD TAPE SEALER NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) GABLE TRIM (GTMH)

BL

PURLIN CLOSURE (TYP.)

1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-T) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER

STC/MSC ROOF PANEL

PURLIN

THERMAL SPACER

(NOT BY CHIEF)

#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR)

PURLIN CLOSURE (GPC) PANEL CLIP w/FASTENERS

#12-14 X 1" PANCAKE HEAD EACH PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

AP SOFFIT PANEL

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B)

GABLE EXTENSION CHANNEL (GEC) EXTENSION GABLE FLASHING (EGFA) 1/4-14 X 7/8" (12" C.C.) **

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

EAVE STRUT

JAMB TRIM (JT) INSIDE CLOSURE ***

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC / MSC

TRIM TYPE EGFA EFHP

L OR H SYSTEM

PURLIN SIZE

PANEL SUPPORT TRIM (SSP) (TYP.) 1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

8

HIGH HIGH

10

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg CS Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE SEALER NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) GABLE TRIM (GTMH) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) (2) 1/4-14 X 7/8"

1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-T) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER

STC/MSC ROOF PANEL

PURLIN

THERMAL SPACER

(NOT BY CHIEF)

#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR)

PURLIN CLOSURE (GPC) PANEL CLIP w/FASTENERS

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

#12-14 X 1" PANCAKE HEAD EACH PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

CS SOFFIT PANEL

GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EFCP) **

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR

EAVE STRUT

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC / MSC

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

TRIM TYPE EFCP ECHP

PURLIN SIZE

L OR H SYSTEM

INSIDE CLOSURE ***

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

8

HIGH HIGH

RAKE ANGLE (A-20-B)

10

EFCP = EXTENSION FLASHING HIGH PROFILE ECHP = EXT. FLASHING HIGH PROFILE

JAMB TRIM (JT)

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg NO Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

STC/MSC ROOF PANEL

PURLIN

THERMAL SPACER

(NOT BY CHIEF)

PURLIN CLOSURE (GPC) PANEL CLIP w/FASTENERS PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

TOP VIEW

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

GABLE EXPANSION TRIM (GET)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C for AP PANEL)

GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

**

INSIDE CLOSURE

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVET TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

EAVE STRUT

***

*** HIGH PROFILE TRIM UNSOFFITED GABLE EXT STC / MSC

L OR H SYSTEM

TRIM TYPE

PURLIN SIZE

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

8

HIGH HIGH

EF

10

EFHP

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

EF- EXTENSION FLASHING EFHP - EXTENSION FLASHING HIGH PROFILE

PURLIN CLOSURE INSTALLATION

WALL PANEL

STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim AP Sof and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

GABLE EXTENSION DIMENSION TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

TRI-BEAD TAPE SEALER 1/4-14 X 7/8" WT (6" C.C.) GABLE TRIM (GTMH) RAKE SUPPORT (A-20-T) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION * 1/4-14 X 1 1/4 SHOULDER(24" C.C.)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN CLOSURE (TYP.)

RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) RAKE SUPPORT (A-20-T) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER * 1/4-14 X 1 1/4 SHOULDER (24" C.C.)

PURLIN STC/MSC ROOF PANEL PURLIN CLOSURE (GPC) PANEL CLIP w/FASTENERS

PURLIN

?

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

THERMAL SPACER

(NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

PANEL SUPPORT TRIM (SSP) (TYP.) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) 10'-0" C.C.)

TOP VIEW

GABLE EXPANSION TRIM (GET)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C for AP PANEL)

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

AP SOFFIT PANEL

EAVE STRUT

INSIDE CLOSURE ***

EXTENSION GABLE FLASHING (EGFA) GABLE EXTENSION CHANNEL (GEC) **

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) JAMB TRIM (JT)

#12-14 X 1 1/4" (12"C.C.) (SOFFIT COLOR)

**

TRIM TYPE EGFA EFHP

PURLIN SIZE

L OR H SYSTEM

WALL PANEL

HIGH PROFILE TRIM-SOFFITED GABLE EXT STC/ MSC

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

8

HIGH HIGH

1/4-14 X 7/8" (12" C.C.) (TYP.)

EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE

10

STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim CS Soffit Thermal Spacer

1

PURLIN

GABLE EXTENSION DIMENSION TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

TRI-BEAD TAPE SEALER 1/4-14 X 7/8" WT (6" C.C.) GABLE TRIM (GTMH) RAKE SUPPORT (A-20-T) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION * 1/4-14 X 1 1/4" SHOULDER (24" C.C.)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

* 1/4-14 X 1 1/4" SHOULDER (24" C.C.) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER

PURLIN STC/MSC ROOF PANEL PURLIN CLOSURE (GPC) PANEL CLIP w/FASTENERS

?

PURLIN

RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) RAKE SUPPORT (A-20-T)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

THERMAL SPACER

(NOT BY CHIEF)

#12-14 X 1 1/4" (12" C.C.)

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

TOP VIEW

(2)1/4-14 X 7/8"

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) GABLE EXTENSION CHANNEL (GEC)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.)

**

HIGH PROFILE TRIM-SOFFITED GABLE EXT STC/ MSC

INSIDE CLOSURE ***

EAVE STRUT

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

1/4-14 X 7/8" (12" C.C.) RAKE ANGLE (A-20-B)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

JAMB TRIM (JT)

WALL PANEL

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

#12-14 X 1" PANCAKE HEAD EACH PURLIN EXTENSION FLASHING (EFCP) **

PANEL CAP TRIM (SCT)

L OR H SYSTEM

TRIM TYPE EFCP ECHP

PURLIN SIZE

EFCP = EXTENSION FLASHING HIGH PROFILE ECHP = EXT. FLASHING HIGH PROFILE

PURLIN CLOSURE INSTALLATION

8

HIGH HIGH

10

STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim NO Sof and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

TRI-BEAD TAPE SEALER 1/4-14 X 7/8" WT (6" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER

PANEL CLIP w/FASTENERS STC/MSC ROOF PANEL PURLIN #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

PURLIN

?

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (12" C.C.) RAKE SUPPORT (A-20-T)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

THERMAL SPACER

(NOT BY CHIEF)

PURLIN CLOSURE (GPC)

TOP VIEW

(2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE WALL PANEL

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) GABLE EXTENSION CHANNEL (GEC)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

**

INSIDE CLOSURE

EAVE STRUT

#12-14 X 1 1/4" (6" C.C. for CS PANEL ) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

EF- EXTENSION FLASHING EFHP - EXTENSION FLASHING HIGH PROFILE

*** HIGH PROFILE TRIM UNSOFFITED GABLE EXT STC / MSC

TRIM TYPE

PURLIN SIZE

L OR H SYSTEM

#12-14 X 1" PANCAKE HEAD EACH PURLIN EXTENSION FLASHING (EF) ***

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

PANEL CAP (SCT)

8

HIGH HIGH

EF

10

EFHP