MVF / MVP - Erection Manual
MVF/MVP M echanically S eamed V ertical Leg F lat M echanically S eamed V ertical Leg P encil-rib
®
SEAMING INSTRUCTIONS
MVF/MVP ROOF PANEL
INSPECTION OF SEAM A visual inspection of the seam should be made to determine if the seam is forming properly. Check seam with the GO GAUGE provided. The gage should easily go on to the formed seam. If it is loose fitting it is O. K.
0.350” Maximum
CROSS SECTION OF FINISHED SEAM
0.350”
MVF/MVP GO GAUGE
GO GAUGE
MVF/MVP ROOF PANEL
GO GAUGE
MVF/MVP ROOF PANEL
.350 MAX
SEAM GO GAUGE
CAUTION IF THE SEAMER IS NOT PRODUCING A FINISHED SEAM THAT PASSES THE GO-GAUGE TEST, STOP AT ONCE AND CALL CHIEF BUILDINGS AT (308) 389-7289. FAILURE TO MAINTAIN AN ACCEPTABLE SEAM COULD RESULT IN FAILURE OF THE ROOF SYSTEM AND WILL VOID ALL WARRANTIES.
CHECK FINISHED SEAM WITH THE GO GAUGE
Version 2.0
MVF/MVP Seaming-4
SUBJECT TO CHANGE WITHOUT NOTICE