MVF MVP Roof Panel
MVF-MVP Inset Gable Tail End Height Change w Cut Roof Panel and Panel Below-Thermal Spacer
ROOF PANEL CUT BACK DIM. CLIP LOCATION FROM B
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
L
CLOSURE CLIPS (GCC-1) (TYP.)
BL
TAPE MASTIC HEIGHT CHANGE TRIM BOTTOM (GHVB) HEIGHT CHANGE TRIM TOP (GHVT)
PURLIN CLOSURE (TYP.)
2 1 4 "
*WALL PANEL INSIDE CLOSURE #12-14 X 1 1/4"
1 1 2 "
1/4-14 X 1 1/4" WT (6" C.C.)** RAKE ANGLE (A-20-B) DOUBLE BEAD TAPE MASTIC (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-L)
PURLIN
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
(2) #12-14 X 1 1/4"' PER CLOSURE
MVF/MVP ROOF PANEL
(NOT BY CHIEF)
THERMAL SPACER
TOP VIEW
1
4 "
PANEL CLIP w/FASTENERS (REFER TO ROOF PANELING PLAN)
DOUBLE BEAD TAPE MASTIC
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
#12-14 1 1/4" (2 EACH PURLIN) (WALL COLOR)
HEIGHT CHANGE RAFTER
PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)
EAVE STRUT
(2) #12-24 X 1 1/2" (36" C.C.)
1/4-14 X 7/8" (12" C.C.) PANELING CAP TRIM (SCT)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
RAKE ANGLE (A-20)
* Field cut bottom of wall panels to match roof slope. Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
PURLIN CLOSURE INSTALLATION
**NOTE: This fastener must not hit the purlin.