STC - Erection Manual
STC S nap T ight C onstruction
®
DETAILS HIP TRIM
RIDGE/HIP FLASH
"Z" CLOSURE (Field cut to length and bevel cut to fit panel) SIKA 201 3" X 3" 16 GA. BACK-UP ANGLE
2" ±2"
1/4"-14 X 7/8" WT (5" C.C.) TRI-BEAD TAPE MASTIC
ROOF CLIP AND FASTENERS (SEE ROOF PANELING PLAN)
STC PANEL
PURLIN
#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)
MIN. 16 GA. PLATE HIP SUPPORT 1/8" X 3/8" BLIND RIVET (4" C.C.)
1/4"-14 X 7/8" WT (5" C.C.)
RIDGE/HIP FLASH
STC PANEL
SIKA-201
MIN. 16 GA. PLATE HIP SUPPORT
"Z" CLOSURE (Field cut to length and bevel cut to fit panel) 1/8" X 3/8" BLIND RIVET (4" C.C.)
TRI-BEAD TAPE MASTIC
A-20-B ANGLE 6" LONG (2)#12-14 X 1 1/4"
3" x 3" X 16 GA. ANGLE
EAVE STRUT
EAVE STRUT
REFER TO ERECTION DRAWINGS FOR PART CALL OUTS CAUTION
All trapezoidal panels are extremely difficult to install at hips and valleys in a weather tight manner. The use of these details should only be attempted by installation crews that are highly experienced. In order to help ensure weather tightness, Chief Building's recommends it’s MVF / MVP standing seam system for use on roofs that require hips and valleys.
STC-56
Version 7.1
SUBJECT TO CHANGE WITHOUT NOTICE