STC MSC Roof Panel
STC-MSC Outset Gable Tail Height Change w Special Trim and Panel Below
INSIDE CLOSURE
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
TRI-BEAD TAPE MASTIC SPECIAL TRIM TOP (SPT-
)
CLOSURE CLIPS (GCC-1) (TYP.)
BL
PURLIN CLOSURE (TYP.)
*WALL PANEL
SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING) (SEE INSET DETAIL)
HEIGHT CHANGE ANGLE (A-20-H)
#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
PURLIN
1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
STC/MSC ROOF PANEL
PURLIN
**
(2) #12-14 X 1 1/4"' PER CLOSURE
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
TOP VIEW
1
4 "
HEIGHT CHANGE TRIM BOTTOM (GHMBF)
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PANEL CLIP
** Drafting note: thermal spacer to be used with no insulation. SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
PURLIN CLOSURE (GPC___) (PURLIN CLOSURE CLIPS NOT SHOWN) #12-14 X 1 1/4" (GA) (2 EACH PURLIN) 1/4-14 X 7/8" (12" C.C.)
EAVE STRUT
HEIGHT CHANGE RAFTER PANELING CAP TRIM (SCT) RAKE ANGLE (A-20)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING)
PURLIN CLOSURE INSTALLATION