STC MSC Roof Panel

STC-MSC Outset Gable Tail Height Change w Special Trim and Panel Below

TRI-BEAD TAPE MASTIC SPECIAL TRIM TOP (SPT- ) INSIDE CLOSURE

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

*WALL PANEL

SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING) (SEE INSET DETAIL)

HEIGHT CHANGE ANGLE (A-20-H)

#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

PURLIN

1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

STC/MSC ROOF PANEL

PURLIN

**

(2) #12-14 X 1 1/4"' PER CLOSURE

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

TOP VIEW

1

4 "

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PANEL CLIP

** Drafting note: thermal spacer to be used with no insulation. SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

PURLIN CLOSURE (GPC___) (PURLIN CLOSURE CLIPS NOT SHOWN) #12-14 X 1 1/4" (GA) (2 EACH PURLIN) 1/4-14 X 7/8" (12" C.C.)

EAVE STRUT

HEIGHT CHANGE RAFTER PANELING CAP TRIM (SCT) RAKE ANGLE (A-20)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION