STC MSC Roof Panel
STC-MSC Inset Gable Height Change w Field Bend Vertical Leg and Thermal Spacer
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) TRI-BEAD TAPE SEALER HEIGHT CHANGE TRIM TOP (GHMTF) INSIDE CLOSURE
HEIGHT CHANGE ANGLE (A-20-H) #12-14 x 1 1/4" * WALL PANEL
BL
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) 1/4-14 X 1 1/4" WT (12" C.C.)
1
4 "
RAKE SUPPORT (A-20-T)
THERMAL SPACER
(NOT BY CHIEF)
PURLIN
HEIGHT CHANGE TRIM BOTTOM (GHMBF) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
2"
1/4-14 X 1 1/4" SHOULDER (24" C.C.)**
** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)
* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.