STC MSC Roof Panel
STC-MSC Inset Gable Height Change w Field Bend Vertical Leg with Panel Below and Thermal Spacer
** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.
PURLIN
STC/MSC ROOF PANEL(FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) 1/4-14 X 1 1/4" WT (12" C.C.) SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) TRI-BEAD TAPE SEALER HEIGHT CHANGE TRIM TOP (GHMTF) INSIDE CLOSURE
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
HEIGHT CHANGE ANGLE (A-20-H) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) * WALL PANEL
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
BL
PURLIN
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
THERMAL SPACER
(NOT BY CHIEF)
(2) #12-14 X 1 1/4"' PER CLOSURE
1
4 "
RAKE SUPPORT (A-20-T)
1/4-14 X 1 1/4" SHOULDER (24" C.C.)** PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) HEIGHT CHANGE TRIM BOTTOM (GHMBF)
TOP VIEW
PURLIN
2"
HEIGHT CHANGE RAFTER
RAKE ANGLE (A-20)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
EAVE STRUT
1/4-14 X 7/8" (12" C.C.) PANELING CAP TRIM (SCT) (2) #12-24 X 1 1/2" AT 36" C.C.
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)
PURLIN CLOSURE INSTALLATION