Composite Material, Rigid Board, R-Seal
CS Metal Bldg Walkdoor-PA-SF Rigid Wall
CS Panel - Rigid Board Insulation in Wall - Metal Building Walkdoor - Pre-Assembled (by Chief) or Self-Framing Not by Chief Refer to Order Documents for Doors by Chief
Installation Steps: 1. Install Wrap Plate. 2. Special Insulation Cover Trim (SPT). 3. Rigid Continuous Insulation. 4. Door. 5. Jamb Trim (JT) with notch at header. 6. Header Trim (HTT). 7. Notch and slit wall panel. 8. Place wall panel over trims with foam inside closure. 9. Cover Trim (COT). 10. Liner Cover Trim (LCT), if applicable. 11. Use with Liner/Backer. 12. Refer to Liner or Partition Panel Drawings.
Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
HEADER TRIM (HTT)
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
1" PANEL SLIT
1" SLIT
2" X 1/4" NOTCH
INSIDE CLOSURE
2" JAMB TRIM NOTCH
Notes: ·
Special Fastener =
#12-14 X ____"
JAMB TRIM (JT)
For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
·
Rigid Continuous Insulation thickness =
X"
· Rigid Continuous Insulation and vapor retarder are not by Chief. · Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. · The details shown are typical. · Not all details may apply. · Specific details for additional features will be provided for complete installation instructions. · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · LCT1 or LCT2 used with Liner/Backer. Refer to Liner or Partition Panel Dwg. · Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
SPECIAL TRIM (SPT-x)
WALL PANEL SLIT
DOOR FRAME
COVER TRIM (COT)
TRIM DETAIL AT CORNERS
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
OPENING WIDTH
OPENING WIDTH
#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)
BL
WALL PANEL
JAMB
JAMB
SPECIAL FASTENER (6" C.C.) INSIDE CLOSURE #12-14 X 1" PANCAKE (7'-0" C.C.)
NOMINAL DOOR OPENING
NOMINAL DOOR OPENING
ZEE GIRT
#12-14 X 1" PANCAKE HEAD (12" C.C.)
RIGID CONTINUOUS INSULATION (NOT BY CHIEF) #12-14 X 1" PANCAKE HEAD (12" C.C.)
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)
DOOR FRAME
DOOR FRAME
HEADER TRIM (HTT)
SPECIAL TRIM (SPT-x)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) SPECIAL TRIM (SPT-x)
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
JAMB TRIM (JT)
BL
BL
* 1 4 "
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)
CUT RIB AS NEEDED
JAMB TRIM (JT)
RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
1
2 " MIN.
DOOR FRAME
CUT RIB AS NEEDED
WALL PANEL SPECIAL FASTENER (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) SPECIAL TRIM (SPT-x)
WALL PANEL SPECIAL FASTENER (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)
***1/8"-3/4"
***1 3/4"-2"
OPENING HEIGHT
NOMINAL
*** Locate JT/COT/HTT trim assembly to cover door frame avoiding interference with latch, door and hinges.
*** Locate JT/COT/HTT trim assembly to so cover trim COT aligns on minor rib. Adjust header widths accordingly.
DOOR OPENING
WALKDOOR HEADER TRIM DETAILS
WALKDOOR JAMB TRIM DETAILS
ALTERNATE WALKDOOR JAMB TRIM DETAILS (Alternate detail for increased door swing clearance)
CEE HEADER