Eave and Gable Extensions
CS Gable Ext Roof Panel Starts Outside Building Line FSP Soffit
IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.
PURLIN
* FIELD CUT AROUND PURLINS FOR ATTACHMENT.
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
NOTE: REMOVE NOTE, RAKE ANGLE & SCREWS AT MID-SPAN OF SOFFIT IF NOT USED!
PURLIN CLOSURE (TYP.)
1
GABLE EXTENSION DIMENSION
BL
2 1 8 "
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (12" C.C.)
?
GABLE TRIM (GTC)
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR)
1"
PURLIN
CS ROOF PANEL
PURLIN
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
* RAKE ANGLE (A-20)
PURLIN CLOSURE (GPC)
(2) #12-14 X 1 1/4"' PER CLOSURE
PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
GABLE EXTENSION CHANNEL (GEC)
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
TOP VIEW
EXTENSION FLASHING (EF)
#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.)
(2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)
FSP SOFFIT PANEL
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
1/4-14 X 7/8" (EACH RIB)
1/8" X 3/8" BLIND RIVET (12" C.C.)
JAMB TRIM/SOFFIT TRIM (JTS) 1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) #12-14 X 1" PANCAKE HEAD (12" C.C.)
NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.
EAVE STRUT
INSIDE CLOSURE **
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
RAKE ANGLE (A-20-B) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)
** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
PURLIN CLOSURE INSTALLATION
WALL PANEL