High Profile Trim
MVF-MVP Gable Ext Tail End w High Profile Trim-AP Soffit and Thermal Spacer
1
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
GABLE EXTENSION DIMENSION
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
ROOF PANEL CUT BACK DIMENSION
* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN.
CLOSURE CLIPS (GCC-1) (TYP.)
BL
PURLIN CLOSURE (TYP.)
* 1/4-14 X 1 1/4" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC
#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) GABLE EXTENSION CHANNEL (GEC) EXTENSION GABLE FLASHING (EGFA) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" PANEL CLIP w/FASTENERS ** GABLE TRIM (GTVH) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4" (WALL COLOR) EACH CLIP CLIP LOCATION FROM SL PANEL SUPPORT TRIM (SSP)
PURLIN
1 3
PANEL CLIP w/FASTENERS
4 "
THERMAL SPACER
(NOT BY CHIEF)
1"
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)
PURLIN
MVF/MVP ROOF PANEL PURLIN CLOSURE (GPC)
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN #12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)
(2) #12-14 X 1 1/4"' PER CLOSURE
TOP VIEW
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
AP SOFFIT PANEL
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) PANEL SUPPORT TRIM (SSP)
INSIDE CLOSURE ***
EAVE STRUT
JAMB TRIM (JT)
PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) RAKE ANGLE (A-20-B)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
HIGH PROFILE TRIM-SOFFITED GABLE EXT MVF/MVP
TRIM TYPE EGFA EFHP
PURLIN SIZE
L OR H SYSTEM
#12-14 X 1" PANCAKE HEAD EACH PURLIN
8
HIGH HIGH
WALL PANEL
*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
10
1/4-14 X 7/8" (12" C.C.) (TYP.)
PURLIN CLOSURE INSTALLATION
EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE