High Profile Trim

MVF-MVP Gable Ext Tail End w High Profile Trim-NO Soffit and Thermal Spacer

PURLIN

1

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

* 1/4-14 X 1 1/4" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC

GABLE TRIM (GTVH) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4" (WALL COLOR) EACH CLIP CLIP LOCATION FROM SL ROOF PANEL CUT BACK DIMENSION

* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN. PANEL CLIP w/FASTENERS

1 3

4 "

PURLIN

#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)

THERMAL SPACER

(NOT BY CHIEF)

1"

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

MVF/MVP ROOF PANEL PURLIN CLOSURE (GPC)

(2) #12-14 X 1 1/4"' PER CLOSURE

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" PANEL CLIP w/FASTENERS

RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN #12-14 X 1" PANCAKE HEAD

TOP VIEW

**

INSIDE CLOSURE

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1" PANCAKE HEAD EACH PURLIN GABLE EXTENSION CHANNEL (GEC) 1/4-14 X 7/8" (12" C.C.)

PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

WALL PANEL

***

#12-14 X 1 1/4" (12" C.C.) EXTENSION FLASHING (EF)

TRIM TYPE

PURLIN SIZE

L OR H SYSTEM

HIGH PROFILE TRIM- UNSOFFITED GABLE EXT MVF/MVP ***

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

8

HIGH HIGH

EF

PURLIN CLOSURE INSTALLATION

10

EFHP

EF- EXTENSION FLASHING EFHP - EXT. FLASHING