MVF MVP Roof Panel
MVF-MVP Outset Gable Lead End Height Change and Panel Below
* Field cut bottom of wall panels to match roof slope. Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
HEIGHT CHANGE TRIM BOTTOM (GHVB) HEIGHT CHANGE TRIM TOP (GHVT) (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR
PURLIN CLOSURE (TYP.)
*WALL PANEL (TYP.) INSIDE CLOSURE #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
BL
MVF/MVP ROOF PANEL DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (6" C.C.)** TAPE MASTIC
PURLIN
PURLIN
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
***
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
1
4 "
(2) #12-14 X 1 1/4"' PER CLOSURE
TOP VIEW
RAKE ANGLE (A-20-L)
PANEL CLIP w/FASTENERS (REFER TO ROOF PANEL PLAN)
(2) #12-14 X 1 1/4"
PANEL CLIP
**NOTE: This fastener must not hit the purlin.
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)
HEIGHT CHANGE RAFTER
PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)
EAVE STRUT
RAKE ANGLE (A-20)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
1/4-14 X 7/8" (12" C.C.)
#12-14 X 1 1/4" (GA) (2 EACH PURLIN)
***DRAFTING NOTE: Thermal spacer to be used with no insulation
PANELING CAP TRIM (SCT)
PURLIN CLOSURE INSTALLATION