MVF MVP Roof Panel

MVF-MVP Outset Gable Lead End Height Change and Panel Below

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

HEIGHT CHANGE TRIM BOTTOM (GHVB) HEIGHT CHANGE TRIM TOP (GHVT) (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR

PURLIN CLOSURE (TYP.)

*WALL PANEL (TYP.) INSIDE CLOSURE #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

BL

MVF/MVP ROOF PANEL DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (12" C.C.)** TAPE MASTIC

PURLIN

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

1

4 "

(2) #12-14 X 1 1/4"' PER CLOSURE

TOP VIEW

RAKE ANGLE (A-20-L)

PANEL CLIP w/FASTENERS (REFER TO ROOF PANEL PLAN)

(2) #12-14 X 1 1/4"

PANEL CLIP

**NOTE: This fastener must not hit the purlin.

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)

HEIGHT CHANGE RAFTER

PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)

EAVE STRUT

RAKE ANGLE (A-20)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (GA) (2 EACH PURLIN)

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

PANELING CAP TRIM (SCT)

PURLIN CLOSURE INSTALLATION