MVF MVP Roof Panel
MVF-MVP High Side Height Change w Cee Girt to Taller Building and Panel Below
#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) WALL PANEL (TYP.)
* For screw spacing refer to High Side Height Change detail in the MVF/MVP Roof Panel Erection manual.
INSIDE CLOSURE
BL
RIDGE CLOSURE *1/4-14 X 7/8" WT EXPANSION TRIM (LHET) DOUBLE BEAD TAPE MASTIC PANEL CLIP w/FASTENERS (REFER TO ROOF PANEL PLAN) PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
1
4 "
**
(2) #12-14 X 1 1/4" (GA) (36" C.C.)
3"
MVF/MVP ROOF PANEL
GIRT
PURLIN DOUBLE BEAD TAPE MASTIC
**DRAFTING NOTE: Thermal spacer to be used with no insulation.
1/4-14 X 7/8" WT (7 PER PANEL)