MVF MVP Roof Panel
MVF-MVP High Side Height Change w Zee Girt to Taller Building and Panel Below
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C for AP PANEL) RAKE ANGLE (A-20-B) WALL PANEL (TYP.)
* For screw spacing refer to High Side Height Change detail in the MVF/MVP Roof Panel Erection manual.
INSIDE CLOSURE
BL
*1/4-14 X 7/8" WT EXPANSION TRIM (LHET)
Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
DOUBLE BEAD TAPE MASTIC
RIDGE CLOSURE
PANEL CLIP w/FASTENERS (REFER TO ROOF PANEL PLAN) PRE-GLUED THERMAL SPACER (NOT BY CHIEF) **
1
4 "
(2) #12-14 X 1 1/4" (GA) (36" C.C.) GIRT
3"
MVF/MVP ROOF PANEL
**DRAFTING NOTE: Thermal spacer to be used with no insulation.
PURLIN DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (7 PER PANEL)
Made with FlippingBook - Online catalogs