High Profile Trim
STC-MSC Gable Ext Tail End High Profile Trim-Field Bend Leg-Term Trim AP Sof and Thermal Spacer
1
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
GABLE EXTENSION DIMENSION TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
TRI-BEAD TAPE SEALER 1/4-14 X 7/8" WT (6" C.C.) GABLE TRIM (GTMH) RAKE SUPPORT (A-20-T) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION * 1/4-14 X 1 1/4 SHOULDER(24" C.C.)
CLOSURE CLIPS (GCC-1) (TYP.)
BL
*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.
PURLIN CLOSURE (TYP.)
RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) RAKE SUPPORT (A-20-T) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER * 1/4-14 X 1 1/4 SHOULDER (24" C.C.)
PURLIN STC/MSC ROOF PANEL PURLIN CLOSURE (GPC) PANEL CLIP w/FASTENERS
PURLIN
?
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
THERMAL SPACER
(NOT BY CHIEF)
(2) #12-14 X 1 1/4"' PER CLOSURE
PANEL SUPPORT TRIM (SSP) (TYP.) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) 10'-0" C.C.)
TOP VIEW
GABLE EXPANSION TRIM (GET)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
1/4-14 X 7/8" (12" C.C.)
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C for AP PANEL)
#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)
AP SOFFIT PANEL
EAVE STRUT
INSIDE CLOSURE ***
EXTENSION GABLE FLASHING (EGFA) GABLE EXTENSION CHANNEL (GEC) **
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)
1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) JAMB TRIM (JT)
#12-14 X 1 1/4" (12"C.C.) (SOFFIT COLOR)
**
TRIM TYPE EGFA EFHP
PURLIN SIZE
L OR H SYSTEM
WALL PANEL
HIGH PROFILE TRIM-SOFFITED GABLE EXT STC/ MSC
*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
PURLIN CLOSURE INSTALLATION
8
HIGH HIGH
1/4-14 X 7/8" (12" C.C.) (TYP.)
EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE