Eave and Gable Extensions

Common details and conditions found at eaves and gable extensions.

Eave and Gable Extensions Sections & Details

All details downloadable in .dwg and .pdf

Table of Contents

CS Roof - Eave Extension CS Low Side Eave Ext w Gutter CS-AP Soffit CS Low Side Eave Ext w Gutter FSP Soffit CS Low Side Eave Ext w Gutter NO Soffit CS Low Side Eave Ext w Oversize Gutter CS-AP Soffit CS Low Side Eave Ext w Oversize Gutter FSP Soffit CS Low Side Eave Ext w Oversize Gutter NO Soffit CS Low Side Eave Ext w Eave Trim CS-AP Soffit CS Low Side Eave Ext w Eave Trim FSP Soffit CS Low Side Eave Ext w Eave Trim NO Soffit CS High Side Eave Ext w Eave Trim CS-AP Soffit CS High Side Eave Ext w Eave Trim FSP Soffit CS High Side Eave Ext w Eave Trim NO Soffit CS Roof - Gable Extension

CS Gable Ext AP Soffit CS Gable Ext CS Soffit CS Gable Ext FSP Soffit CS Gable Ext NO Soffit

CS Gable Ext Only on HS with Eave Trim 2 to 12 and Over No Soffit CS Gable Ext Only on HS with Eave Trim Less than 2 to 12 No Soffit CS Gable Ext Roof Panel Starts Outside Building Line AP Soffit CS Gable Ext Roof Panel Starts Outside Building Line CS Soffit CS Gable Ext Roof Panel Starts Outside Building Line FSP Soffit CS Gable Ext Roof Panel Starts Outside Building Line NO Soffit STC-MSC Roof - Eave Extension

STC-MSC Low Side Eave Ext w Eave Gutter and CS-AP Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Eave Gutter and FSP Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Eave Gutter and NO Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Eave Trim and CS-AP Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Eave Trim and FSP Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Eave Trim and NO Soffit and Thermal STC-MSC Low Side Eave Ext w Oversize Gutter and CS-AP Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Oversize Gutter and FSP Soffit and Thermal Spacer STC-MSC Low Side Eave Ext w Oversize Gutter and NO Soffit and Thermal Spacer STC-MSC High Side Eave Ext w Eave Trim and CS-AP Soffit and Thermal Spacer STC-MSC High Side Eave Ext w Eave Trim and NO Soffit and Thermal Spacer STC-MSC High Side Eave Ext w Eave Trim FSP Soffit and Thermal Spacer STC-MSC Roof - Gable Extension - Short Clip

STC-MSC Gable Ext Lead End w AP Soffit STC-MSC Gable Ext Lead End w CS Soffit

Table of Contents

STC-MSC Gable Ext Lead End w FSP Soffit STC-MSC Gable Ext Lead End w NO Soffit STC-MSC Gable Ext Only at High Side w NO Soffit STC-MSC Gable Ext Tail End w AP Soffit STC-MSC Gable Ext Tail End w CS Soffit STC-MSC Gable Ext Tail End w FSP Soffit STC-MSC Gable Ext Tail End w NO Soffit

STC-MSC Gable Ext Tail End-Field Bend Vertical Leg w AP Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg w CS Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg w FSP Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg w NO Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg-Term Trim w AP Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg-Term Trim w CS Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg-Term Trim w FSP Soffit STC-MSC Gable Ext Tail End-Field Bend Vertical Leg-Term Trim w NO Soffit STC-MSC Gable Ext Tail End-Termination Trim w AP Soffit STC-MSC Gable Ext Tail End-Termination Trim w CS Soffit STC-MSC Gable Ext Tail End-Termination Trim w FSP Soffit STC-MSC Gable Ext Tail End-Termination Trim w NO Soffit STC-MSC Roof - Gable Extension - Tall Clip (w Thermal Spacer)

STC-MSC Gable Ext Lead End w AP Soffit and Thermal Spacer STC-MSC Gable Ext Lead End w CS Soffit and Thermal Spacer STC-MSC Gable Ext Lead End w FSP Soffit and Thermal Spacer STC-MSC Gable Ext Lead End w NO Soffit and Thermal Spacer

STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w FSP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w NO Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg-Term Trim w AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg-Term Trim w CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg-Term Trim w FSP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Field Bend Vertical Leg-Term Trim w NO Soffit and Thermal Spacer

STC-MSC Gable Ext Tail End -Term Trim w AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Term Trim w CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Term Trim w FSP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End -Term Trim w NO Soffit and Thermal Spacer STC-MSC Gable Ext Tail End w AP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End w CS Soffit and Thermal Spacer STC-MSC Gable Ext Tail End w FSP Soffit and Thermal Spacer STC-MSC Gable Ext Tail End w NO Soffit and Thermal Spacer

Table of Contents

MVF-MVP Roof - Eave Extension MVF-MVP Low Side Eave Ext w Eave Gutter CS-AP Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Eave Gutter FSP Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Eave Gutter NO Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Eave Trim CS-AP Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Eave Trim FSP Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Eave Trim NO Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Oversize Gutter CS-AP Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Oversize Gutter FSP Soffit and Thermal Spacer MVF-MVP Low Side Eave Ext w Oversize Gutter NO Soffit and Thermal Spacer MVF-MVP High Side Eave Ext w Eave Trim CS-AP Soffit and Thermal Spacer MVF-MVP High Side Eave Ext w Eave Trim FSP Soffit and Thermal Spacer MVF-MVP High Side Eave Ext w Eave Trim NO Soffit and Thermal Spacer MVF-MVP Roof - Gable Extension - Short Clip MVF-MVP Gable Ext Lead End w AP Soffit MVF-MVP Gable Ext Lead End w FSP Soffit MVF-MVP Gable Ext Lead End w NO Soffit MVF-MVP Gable Ext Only at High Side Eave Strut and NO Soffit MVF-MVP Gable Ext Tail End w AP Soffit MVF-MVP Gable Ext Tail End w CS Soffit MVF-MVP Gable Ext Tail End w FSP Soffit MVF-MVP Gable Ext Tail End w NO Soffit MVF-MVP Roof - Gable Extension - Tall Clip (w Thermal Spacer) MVF-MVP Gable Ext Lead End w AP Soffit and Thermal Spacer MVF-MVP Gable Ext Lead End w CS Soffit and Thermal Spacer MVF-MVP Gable Ext Lead End w FSP Soffit and Thermal Spacer MVF-MVP Gable Ext Lead End w NO Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w AP Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w CS Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w FSP Soffit and Thermal Spacer MVF-MVP Gable Ext Tail End w NO Soffit and Thermal Spacer Low Side Eave Extension Only - Horizontal Soffit - Steel Framing

Eave Ext Horiz Soff Low Steel - Interior Frame w Soffit Angle Eave Ext Horiz Soff Low Steel - Interior Frame w Soffit Purlin Eave Ext Horiz Soff Low Steel - Inset Rafter w Soffit Angle Left Eave Ext Horiz Soff Low Steel - Inset Rafter w Soffit Purlin Left

Eave Ext Horiz Soff Low Steel - Bypass Rafter 1'-2 and Less w Soffit Angle Left Eave Ext Horiz Soff Low Steel - Bypass Rafter Greater than 1'-2 w Soffit Angle Left Eave Ext Horiz Soff Low Steel - Bypass Rafter w Soffit Purlin Left Eave Ext Horiz Soff Low Steel - Bypass Rafter 1'-2 and Less with Soffit Angle Right

Table of Contents

Eave Ext Horiz Soff Low Steel - Bypass Rafter Greater than 1'-2 with Soffit Angle Right Eave Ext Horiz Soff Low Steel - Bypass Rafter w Soffit Purlin Right Eave Ext Horiz Soff Low Steel - Inset Rafter w Soffit Angle Right Eave Ext Horiz Soff Low Steel - Inset Rafter w Soffit Purlin Right Low Side Eave Extension Only - Horizontal Soffit - Corners Eave Ext Horiz Soff Low at Corner - AP Wall Panel at Left EW Eave Ext Horiz Soff Low at Corner - CS Wall Panel at Left EW Low Side Eave Extension Only - Horizontal FSP Soffit through Extension Gable Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Bypass Gable and CS Roof High Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Bypass Gable and CS Roof Low Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Bypass Gable and SS Roof High Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Bypass Gable and SS Roof Low Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Inset Gable and CS Roof High Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Inset Gable and CS Roof Low Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Inset Gable and SS Roof High Pitch Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Inset Gable and SS Roof Low Pitch Low Side Eave Extension Only - Horizontal FSP Soffit and CS Roof - Eave Eave Ext Horiz Soff Low CS - FSP Soffit w Eave Gutter Eave Ext Horiz Soff Low CS - FSP Soffit w Eave Trim Eave Ext Horiz Soff Low CS - FSP Soffit w Oversize Gutter Low Side Eave Extension Only - Horizontal FSP Soffit and MVF-MVP Roof - Eave Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Eave Trim and Thermal Spacer Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Eave Trim Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Gutter and Thermal Spacer Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Gutter Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Oversize Gutter and Thermal Spacer Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Oversize Gutter Low Side Eave Extension Only - Horizontal FSP Soffit and STC-MSC Roof - Eave Eave Ext Horiz Soff Low STC-MSC - FSP Soffit w Eave Trim and Thermal Spacer Eave Ext Horiz Soff Low STC-MSC - FSP Soffit w Eave Trim Eave Ext Horiz Soff Low STC-MSC - FSP Soffit w Gutter and Thermal Spacer Eave Ext Horiz Soff Low STC-MSC - FSP Soffit w Gutter Eave Ext Horiz Soff Low STC-MSC - FSP Soffit w Oversize Gutter and Thermal Spacer Eave Ext Horiz Soff Low STC-MSC - FSP Soffit w Oversize Gutter

CS Roof - Eave Extension

CSRoof Eave Extension

CS Low Side Eave Ext w Gutter CS-AP Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1/4-14 X 1 1/4" WT (6" C.C.)

1

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

8 11

(2) 1/4-14 X 1 1/4" WT EACH STRAP

16 "

BL

1/4-14 X 1 1/4" WT (__" C.C.)

GUTTER STRAP (GS) (___" C.C.) 1/4-14 X 7/8" WT (6" C.C.)

CS ROOF PANEL

2 3

(2) 1/4-14 X 7/8" WT EACH STRAP INSIDE CLOSURE

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

4 "

1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 7/8" WT (6" C.C.)

(1) 1/4-14 X 7/8" (TRIM COLOR)

1"

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

CS INSIDE CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

TAPE MASTIC ON TOP OF CLOSURE

**

EAVE GUTTER (EGA) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

INSIDE CLOSURE

EAVE GUTTER (EGA)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.)

SOFFIT PANEL

EAVE EXTENSION FLASHING (EEFA) 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) (TYP.) 1/4-14 X 1 1/4" WT (6" C.C.)

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER

EXTENSION FLASHING (EF)

1/4-14 X 7/8" (12" C.C.)

EXTENSION FLASHING (EF)

CS INSIDE CLOSURE

OUTSIDE CLOSURE

WALL PANEL

EAVE EXTENSION FLASHING (EEFA)

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE GUTTER AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE GUTTER AT EAVE EXTENSION

CS Low Side Eave Ext w Gutter FSP Soffit

CS ROOF PANEL

1

(2) 1/4-14 X 1 1/4" WT EACH STRAP

TAPE MASTIC AT PANEL LAP

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

NOTE: IF INTERMEDIATE PURLIN IS REQUIRED, CHG PURLIN AND ALL FASTENERS TO "DIM" LAYER.

1/4-14 X 1 1/4" WT (6" C.C.)

16 "

8 11

BL

INSIDE CLOSURE

GUTTER STRAP (GS) (___" C.C.) 1/4-14 X 7/8" WT (6"C.C.)

1/4-14 X 1 1/4" WT (6" C.C.) (2) 1/4-14 X 7/8" WT EACH STRAP

2 3

4 "

1/4-14 X 1 1/4" WT (__" C.C.)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

(1) 1/4-14 X 7/8" (TRIM COLOR)

1/4-14 X 7/8" WT (6" C.C.)

CS ROOF PANEL

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 1 1/4" WT (6" C.C.)

1"

CS INSIDE CLOSURE

TAPE MASTIC ON TOP OF CLOSURE

EAVE GUTTER (EGA) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

**INSIDE CLOSURE

EAVE GUTTER (EGA)

FSP SOFFIT PANEL #12-14 X 1" PANCAKE HEAD (12" C.C.)

OUTSIDE CLOSURE

EAVE EXTENSION FLASHING (EEFA)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) EXTENSION FLASHING (EF) 1/4-14 X 7/8" (12" C.C.)

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER EXTENSION FLASHING (EF)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

SOFFIT TRIM (SBLTO) 1/8" X 3/8" BLIND RIVET (12" C.C.)

CS INSIDE CLOSURE

1/8" x 3/8" BLIND RIVET (12" C.C.)

WALL PANEL

EAVE EXTENSION FLASHING (EEFA)

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE GUTTER AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE GUTTER AT EAVE EXTENSION

CS Low Side Eave Ext w Gutter NO Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1/4-14 X 1 1/4" WT (6" C.C.)

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

1

CS ROOF PANEL

8 11

16 "

PANEL CAP TRIM (SCT) INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

GUTTER STRAP (GS) (___" C.C.) 1/4-14 X 7/8" WT (6" C.C.)

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

BL

2 3

4 "

NOTE: JAMB TRIM AROUND EXTENSION BEAM AS REQUIRED.

1/4-14 X 7/8" WT (6" C.C.)

(1) 1/4-14 X 7/8" (TRIM COLOR)

1"

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

TAPE MASTIC ON TOP OF CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 1 1/4" WT (6" C.C.)

(2) 1/4-14 X 7/8" WT EACH STRAP

1/4-14 X 1 1/4" WT (6" C.C.)

EAVE GUTTER (EGA)

EAVE GUTTER (EGA) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.)

(2) 1/4-14 X 1 1/4" WT EACH STRAP

**

INSIDE CLOSURE

#12-14 X 1 1/4" (12" C.C.)

TAPE MASTIC ON BOTTOM OF CLOSURE

1/4-14 X 7/8" (12" C.C.)

EAVE MEMBER EXTENSION FLASHING (EF)

WALL PANEL

EAVE EXTENSION FLASHING (EEFA)

CS INSIDE CLOSURE

EXTENSION FLASHING (EF)

EAVE EXTENSION FLASHING (EEFA)

PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE GUTTER AT EAVE EXTENSION

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE GUTTER AT EAVE EXTENSION".

CS Low Side Eave Ext w Oversize Gutter CS-AP Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

(1) 1/4-14 X 7/8" (TRIM COLOR) GUTTER STRAP (GSO) (1'-0" C.C.) 1/4-14 X 7/8" WT (6" C.C.) * INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM ** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

1/4-14 X 1 1/4" WT (6" C.C.)

1

(2) 1/4-14 X 1 1/4" WT EACH STRAP INSIDE CLOSURE (2) 1/4-14 X 7/8" WT EACH STRAP

16 "

8 11

1/4-14 X 1 1/4" WT (__" C.C.)

BL

2 3

CS ROOF PANEL

4 "

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 7/8" WT (6" C.C.)

1"

CS INSIDE CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

TAPE MASTIC ON TOP OF CLOSURE

OVERSIZED GUTTER (EGAO)

**

INSIDE CLOSURE

OVERSIZED EAVE GUTTER (EGAO)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

SOFFIT PANEL

OUTSIDE CLOSURE

#12-14 X 1 1/4" (12" C.C.) (TYP.) 1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 7/8" WT (12" C.C.) EAVE EXTENSION FLASHING (EEFA)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.)

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER EXTENSION FLASHING (EF)

EXTENSION FLASHING (EF)

1/4-14 X 7/8" (12" C.C.)

CS INSIDE CLOSURE

OUTSIDE CLOSURE

EAVE EXTENSION FLASHING (EEFA)

WALL PANEL

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH OVERSIZED EAVE GUTTER AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH OVERSIZED EAVE GUTTER AT EAVE EXTENSION

CS Low Side Eave Ext w Oversize Gutter FSP Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1

1/4-14 X 1 1/4" WT (6" C.C.)

NOTE: IF INTERMEDIATE PURLIN IS REQUIRED, CHG PURLIN AND ALL FASTENERS TO "DIM" LAYER.

(1) 1/4-14 X 7/8" (TRIM COLOR) GUTTER STRAP (GSO) (1'-0" C.C.) 1/4-14 X 7/8" WT (6" C.C.) * INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM ** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) 1/4-14 X 1 1/4" WT EACH STRAP INSIDE CLOSURE

8 11

16 "

BL

2 3

4 "

1/4-14 X 1 1/4" WT (__" C.C.)

1/4-14 X 1 1/4" WT (6" C.C.) (2) 1/4-14 X 7/8" WT EACH STRAP

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

CS ROOF PANEL

1/4-14 X 7/8" WT (6" C.C.)

1"

CS INSIDE CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 1 1/4" WT (6" C.C.)

TAPE MASTIC ON TOP OF CLOSURE

**

OVERSIZED GUTTER (EGAO)

OVERSIZED EAVE GUTTER (EGAO)

INSIDE CLOSURE

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE

FSP SOFFIT PANEL # 12-14 X 1" PANCAKE HEAD (12" C.C.)

1/8"X 3/8" BLIND RIVET (12" C.C.) 1/4-14 X 7/8" (12" C.C.) EXTENSION FLASHING (EF) EAVE EXTENSION FLASHING (EEFA)

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER EXTENSION FLASHING (EF)

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

SOFFIT TRIM (SBLTO) 1/8" X 3/8" BLIND RIVET (12" C.C.)

CS INSIDE CLOSURE

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

EAVE EXTENSION FLASHING (EEFA)

WALL PANEL

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH OVERSIZED EAVE GUTTER AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH OVERSIZED EAVE GUTTER AT EAVE EXTENSION

CS Low Side Eave Ext w Oversize Gutter NO Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1/4-14 X 1 1/4" WT (6" C.C.)

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

1

8 11

CS ROOF PANEL

16 "

BL

PANEL CAP TRIM (SCT)

GUTTER STRAP (GSO) (1'-0"C.C.) 1/4-14 X 7/8" WT (6" C.C.)

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

2 3

4 "

INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

NOTE: JAMB TRIM AROUND EXTENSION BEAM AS REQUIRED.

1/4-14 X 7/8" WT (6" C.C.)

(1) 1/4-14 X 7/8" (TRIM COLOR)

1"

TAPE MASTIC ON TOP OF CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 1 1/4" WT (6" C.C.)

(2) 1/4-14 X 1 1/4" WT EACH STRAP 1/4-14 X 1 1/4" WT (6" C.C.) (2) 1/4-14 X 7/8" WT EACH STRAP

OVERSIZED EAVE GUTTER (EGA0)

OVERSIZED GUTTER (EGAO)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.)

**

INSIDE CLOSURE

TAPE MASTIC ON BOTTOM OF CLOSURE

1/4-14 X 7/8" (12" C.C.)

EAVE MEMBER EXTENSION FLASHING (EF)

EAVE EXTENSION FLASHING (EEFA)

WALL PANEL

CS INSIDE CLOSURE

EXTENSION FLASHING (EF)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

EAVE EXTENSION FLASHING (EEFA)

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH OVERSIZED EAVE GUTTER AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH OVERSIZED EAVE GUTTER AT EAVE EXTENSION

CS Low Side Eave Ext w Eave Trim CS-AP Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1/4-14 X 1 1/4" WT (6" C.C.)

1

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

BL

5"

1/4-14 X 1 1/4" WT (__" C.C.)

1/4-14 X 1 1/4" WT (6" C.C.) INSIDE CLOSURE

PIGTAIL TAPE MASTIC (Extend pigtail tape mastic from tape mastic at panel lap down purlin bearing leg of panel to marry in with tape mastic on top of closure.)

CS ROOF PANEL

1/4-14 X 7/8" WT (12" C.C.)

1/4-14 X 7/8" WT (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 1 1/4" WT (6" C.C.)

EXTENSION FLASHING (EF) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) ** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM. EAVE TRIM (ETA)

CS INSIDE CLOSURE

2"

TAPE MASTIC ON TOP OF CLOSURE

**

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (ESTO) OUTSIDE CLOSURE INSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.)

SOFFIT PANEL

EAVE TRIM (ETA)

1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TYP.)

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER

OUTSIDE CLOSURE

EXTENSION FLASHING (EF)

CS INSIDE CLOSURE

WALL PANEL

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE TRIM AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE TRIM AT EAVE EXTENSION

CS Low Side Eave Ext w Eave Trim FSP Soffit

CS ROOF PANEL

1

TAPE MASTIC AT PANEL LAP

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

NOTE: IF INTERMEDIATE PURLIN IS REQUIRED, CHG PURLIN AND ALL FASTENERS TO "DIM" LAYER.

1/4-14 X 1 1/4" WT (6" C.C.)

BL

INSIDE CLOSURE

5"

1/4-14 X 1 1/4" WT (__" C.C.)

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

PIGTAIL TAPE MASTIC (Extend pigtail tape mastic from tape mastic at panel lap down purlin bearing leg of panel to marry in with tape mastic on top of closure.)

1/4-14 X 7/8" WT (12" C.C.)

1/4-14 X 7/8" WT (12" C.C.)

CS ROOF PANEL

1/4-14 X 1 1/4" WT (6" C.C.)

CS INSIDE CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

2"

EAVE TRIM (ETA)

TAPE MASTIC ON TOP OF CLOSURE

1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

INSIDE CLOSURE **

FSP SOFFIT PANEL #12-14 X 1" PANCAKE HEAD (12"C.C. 1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

EAVE TRIM (ETA)

EXTENSION FLASHING (EF)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER

SOFFIT TRIM (SBLTO)

1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

EXTENSION FLASHING (EF)

CS INSIDE CLOSURE

1/8" X 3/8" BLIND RIVET (12" C.C.)

WALL PANEL

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE TRIM AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE TRIM AT EAVE EXTENSION

CS Low Side Eave Ext w Eave Trim NO Soffit

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1/4-14 X 1 1/4" WT (6" C.C.)

1

PANEL CAP TRIM (SCT) CS ROOF PANEL INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

BL

5"

PIGTAIL TAPE MASTIC (Extend pigtail tape mastic from tape mastic at panel lap down purlin bearing leg of panel to marry in with tape mastic on top of closure.)

* INSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 7/8" WT (12" C.C.)

1/4-14 X 7/8" WT (12" C.C.)

2"

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 1 1/4" WT (6" C.C.)

TAPE MASTIC ON TOP OF CLOSURE

NOTE: JAMB TRIM AROUND EXTENSION BEAM AS REQUIRED.

EAVE TRIM (ETA)

#12-14 X 1 1/4" (12" C.C.) EXTENSION FLASHING (EF) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

EAVE TRIM (ETA)

**

INSIDE CLOSURE

1/4-14 X 7/8" (12" C.C.)

TAPE MASTIC ON BOTTOM OF CLOSURE

WALL PANEL

EAVE MEMBER

EXTENSION FLASHING (EF)

CS INSIDE CLOSURE

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE TRIM AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH EAVE TRIM AT EAVE EXTENSION

CS High Side Eave Ext w Eave Trim CS-AP Soffit

CS ROOF PANEL

1/4-14 X 7/8" WT (12" C.C.)

1 1

2 "

1

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 1 1/4" WT (6" C.C.) INSIDE CLOSURE

1/4-14 X 7/8" WT (12" C.C.) EAVE TRIM (HSEC)

1/4-14 X 1 1/4" WT (6" C.C.)

BL

1/4-14 X 1 1/4" WT (__" C.C.)

CS ROOF PANEL

TAPE MASTIC AT PANEL LAP

1/4-14 X 1 1/4" WT (6" C.C.)

* OUTSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM 1/4-14 X 7/8" (12" C.C.)

HIGHSIDE EAVE TRIM (HSEC)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

TAPE MASTIC ON TOP OF CLOSURE

CS INSIDE CLOSURE

**

1/4-14 X 7/8" (12" C.C.) EXTENSION FLASHING (EF)

INSIDE CLOSURE

SOFFIT PANEL

1"

CS OUTSIDE CLOSURE

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE

#12-14 X 1 1/4" (12" C.C.) (TYP.)

TAPE MASTIC ON BOTTOM OF CLOSURE

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

OUTSIDE CLOSURE

SOFFIT TRIM (ESTA)

EAVE MEMBER

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

1/4-14 X 7/8" (12" C.C.)

EXTENSION FLASHING (EF)

WALL PANEL

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM AT EAVE EXTENSION

CS High Side Eave Ext w Eave Trim FSP Soffit

NOTE: IF INTERMEDIATE PURLIN IS REQUIRED, CHG PURLIN AND ALL FASTENERS TO "DIM" LAYER.

1

1 1

2 "

CS ROOF PANEL

1/4-14 X 7/8" WT (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 1 1/4" WT (6" C.C.) INSIDE CLOSURE

1/4-14 X 7/8" WT (12" C.C.) * OUTSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

BL

1/4-14 X 1 1/4" WT (__" C.C.)

1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

EAVE TRIM (HSEC)

1/4-14 X 1 1/4" WT (6" C.C.)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

TAPE MASTIC AT PANEL LAP

CS ROOF PANEL

HIGHSIDE EAVE TRIM (HSEC)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1" PANCAKE HEAD (12" C.C. (TYP.) 1/8" X 3/8" BLIND RIVET (12" C.C.) EXTENSION FLASHING (EF)

**

TAPE MASTIC ON TOP OF CLOSURE

INSIDE CLOSURE

FSP SOFFIT PANEL #12-14 X 1" PANCAKE HEAD (12" C.C.)

CS INSIDE CLOSURE

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE

1"

CS OUTSIDE CLOSURE

TAPE MASTIC ON BOTTOM OF CLOSURE

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

SOFFIT TRIM (SBLTA)

1/8" X 3/8" BLIND RIVET (12" C.C.)

EAVE MEMBER

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

WALL PANEL

EXTENSION TRIM FLASHING (EF)

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM AT EAVE EXTENSION

CS High Side Eave Ext w Eave Trim NO Soffit

1

CS ROOF PANEL

1 1

2 "

1/4-14 X 7/8" WT (12" C.C.)

CS ROOF PANEL

1/4-14 X 7/8" WT (12" C.C.) * OUTSIDE CLOSURE WITH TAPE MASTIC TOP & BOTTOM

BL

1/4-14 X 1 1/4" WT (6" C.C.) INSIDE CLOSURE WITH MASTIC TOP AND BOTTOM PANEL CAP TRIM (SCT)

1/4-14 X 1 1/4" WT (6" C.C.)

1/4-14 X 1 1/4" WT (6" C.C.)

#12-14 X 1 1/4" (12" C.C.)

TAPE MASTIC AT PANEL LAP

NOTE: JAMB TRIM AROUND EXTENSION BEAM AS REQUIRED

EAVE TRIM (HSEC)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

HIGHSIDE EAVE TRIM (HSEC)

1/4-14 X 7/8" (12" C.C.)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

**

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) EXTENSION FLASHING (EF)

INSIDE CLOSURE

TAPE MASTIC ON TOP OF CLOSURE

1/4-14 X 7/8" (12" C.C.)

1"

CS OUTSIDE CLOSURE

WALL PANEL

TAPE MASTIC ON BOTTOM OF CLOSURE

EAVE MEMBER

PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)

EXTENSION FLASHING (EF)

* See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM AT EAVE EXTENSION".

PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM AT EAVE EXTENSION

CS Roof - Gable Extension

CSRoof Gable Extension

CS Gable Ext AP Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

1

CS ROOF PANEL

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

PURLIN

BL

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR)

1/4-14 X 7/8" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC #12-14 X 1" PANCAKE HEAD EACH PURLIN

PURLIN CLOSURE (GPC)

2 1 8 "

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

PURLIN

GABLE TRIM (GTC)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4"' PER CLOSURE

1"

GABLE EXTENSION CHANNEL (GEC)

TOP VIEW

#12-14 X 1 1/4"(12" C.C.) (SOFFIT COLOR) EXTENSION FLASHING (EF) PANEL SUPPORT TRIM (SSP)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) AP SOFFIT PANEL

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (12" C.C.) PANEL SUPPORT TRIM (SSP)

1/4-14 X 7/8" (12" C.C.)

INSIDE CLOSURE *

EAVE STRUT

JAMB TRIM (JT)

RAKE ANGLE (A-20-B) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) WALL PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

* DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

CS Gable Ext CS Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

1

PURLIN CLOSURE (TYP.)

PURLIN

GABLE EXTENSION DIMENSION

BL

PURLIN CLOSURE (GPC)

1/4-14 X 7/8" (12" C.C.) GABLE TRIM (GTC) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR)

1/4-14 X 7/8" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC

2 1 8 "

(2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED)

PURLIN

CS ROOF PANEL

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

* DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

1"

(2) #12-14 X 1 1/4"' PER CLOSURE

GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EFC)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

TOP VIEW

CS SOFFIT PANEL

PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) JAMB TRIM (JT) 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" PANCAKE HEAD EACH PURLIN

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1 1/4" (12" C.C.)

INSIDE CLOSURE *

EAVE STRUT

RAKE ANGLE (A-20-B)

WALL PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PURLIN CLOSURE INSTALLATION

CS Gable Ext FSP Soffit

CS ROOF PANEL FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER. IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

1

* FIELD CUT AROUND PURLINS FOR ATTACHMENT.

PURLIN CLOSURE (TYP.)

BL

GABLE EXTENSION DIMENSION

1/4-14 X 7/8" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

2 1 8 "

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM (GTC)

PURLIN

PURLIN

PURLIN CLOSURE (GPC)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

* RAKE ANGLE (A-20)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED)

TOP VIEW

1"

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

GABLE EXTENSION CHANNEL (GEC)

#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) EXTENSION FLASHING (EF)

1/4-14 X 7/8" (EACH RIB)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

JAMB TRIM/SOFFIT TRIM (JTS) 1/8" X 3/8" BLIND RIVET(12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) #12-14 X 1" PANCAKE HEAD (12" C.C.)

RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PANEL CAP TRIM (SCT) WALL PANEL 1/4-14 X 7/8" (12" C.C.) INSIDE CLOSURE **

FSP SOFFIT PANEL

EAVE STRUT

1/8" X 3/8" BLIND RIVET (12" C.C.)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

CS Gable Ext NO Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

1

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN * DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM. #12-14 X 1" PANCAKE HEAD (EACH PURLIN) PURLIN CLOSURE (GPC) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED)

BL

1/4-14 X 7/8" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC

#12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

2 1 8 "

CS ROOF PANEL

PURLIN

PURLIN

GABLE TRIM (GTC)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

1"

1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4"' PER CLOSURE

INSIDE CLOSURE *

TOP VIEW

GABLE EXTENSION CHANNEL (GEC)

PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

EXTENSION FLASHING (EF)

#12-14 X 1" PANCAKE HEAD EACH PURLIN #12-14 X 1 1/4" (12" C.C.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

WALL PANEL

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PURLIN CLOSURE INSTALLATION

CS Gable Ext Only on HS with Eave Trim 2 to 12 and Over No Soffit

1

BL

INSIDE CLOSURE 1/4-14 X 7/8" WT (12" C.C.)

OUTSIDE CLOSURE w/ TAPE MASTIC TOP AND BOTTOM HIGH SIDE EAVE TRIM (HSEC)

1 1 2 "

CS ROOF PANEL

1/4-14 X 7/8" (12" C.C.) 1/4-14 X 7/8" (12" C.C.) EAVE CLOSURE TRIM (ECT)

1/4-14 X 1 1/4" WT (6" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

EAVE STRUT

GABLE EXTENSION EAVE FLASHING (GHBB)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

CS Gable Ext Only on HS with Eave Trim Less than 2 to 12 No Soffit

1

CS ROOF PANEL INSIDE CLOSURE 1/4-14 X 7/8" WT (12" C.C.)

BL

1 1

HI-SIDE EAVE TRIM (HSEC) OUTSIDE CLOSURE w/ TAPE MASTIC TOP AND BOTTOM

2 "

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 1 1/4" WT (6" C.C.) GABLE EXTENSION EAVE FLASHING (GHBA) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) EAVE STRUT

1/4-14 X 7/8" (12" C.C.)

CS Gable Ext Roof Panel Starts Outside Building Line AP Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

1

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

* DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

GABLE TRIM (GTC)

CLOSURE CLIPS (GCC-1) (TYP.)

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (TYP.)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR)

BL

2 1 8 "

#12-14 X 1" PANCAKE HEAD EACH PURLIN DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (12" C.C.)

?

PURLIN

1"

PURLIN CLOSURE (GPC)

PURLIN

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

CS ROOF PANEL

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

GABLE EXTENSION CHANNEL (GEC)

(2) #12-14 X 1 1/4"' PER CLOSURE

EXTENSION FLASHING (EF)

TOP VIEW

(2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) PANEL SUPPORT (SSP) 1/4-14 X 7/8" (12" C.C.)

AP SOFFIT PANEL

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

INSIDE CLOSURE *

1/4-14 X 7/8" (12" C.C.) PANEL SUPPORT TRIM (SSP)

RAKE ANGLE (A-20-B) 1/4-14 x 7/8" (12" C.C.)

EAVE STRUT

JAMB TRIM (JT)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PANEL CAP TRIM (SCT)

WALL PANEL

PURLIN CLOSURE INSTALLATION

CS Gable Ext Roof Panel Starts Outside Building Line CS Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

* DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

1

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

BL

1/4-14 X 7/8" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC

2 1 8 "

1/4-14 X 7/8" (12" C.C.) GABLE TRIM (GTC) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR)

?

PURLIN CLOSURE (GPC)

CS ROOF PANEL

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

PURLIN

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

1"

(2) #12-14 X 1 1/4"' PER CLOSURE

TOP VIEW

GABLE EXTENSION CHANNEL (GEC)

(2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1" PANCAKE HEAD EACH PURLIN

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

EXTENSION FLASHING (EFC)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

JAMB TRIM (JT)

#12-14 X 1 1/4" (12" C.C.)

INSIDE CLOSURE *

1/4-14 X 7/8" (12" C.C.)

EAVE STRUT

RAKE ANGLE (A-20-B) PANEL CAP TRIM (SCT) WALL PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PURLIN CLOSURE INSTALLATION

CS Gable Ext Roof Panel Starts Outside Building Line FSP Soffit

IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.

PURLIN

* FIELD CUT AROUND PURLINS FOR ATTACHMENT.

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

NOTE: REMOVE NOTE, RAKE ANGLE & SCREWS AT MID-SPAN OF SOFFIT IF NOT USED!

PURLIN CLOSURE (TYP.)

1

GABLE EXTENSION DIMENSION

BL

2 1 8 "

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (12" C.C.)

?

GABLE TRIM (GTC)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR)

1"

PURLIN

CS ROOF PANEL

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

* RAKE ANGLE (A-20)

PURLIN CLOSURE (GPC)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

GABLE EXTENSION CHANNEL (GEC)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

TOP VIEW

EXTENSION FLASHING (EF)

#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.)

(2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

FSP SOFFIT PANEL

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1/4-14 X 7/8" (EACH RIB)

1/8" X 3/8" BLIND RIVET (12" C.C.)

JAMB TRIM/SOFFIT TRIM (JTS) 1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) #12-14 X 1" PANCAKE HEAD (12" C.C.)

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

EAVE STRUT

INSIDE CLOSURE **

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

RAKE ANGLE (A-20-B) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL

CS Gable Ext Roof Panel Starts Outside Building Line NO Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

1

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

BL

2 1 8 "

1/4-14 X 7/8" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC

?

PURLIN CLOSURE (GPC) #12-14 X 1" PANCAKE HEAD (EACH PURLIN)

GABLE TRIM (GTC)

#12-14 X 1 1/4" (2 PER PURLIN) (WALL COLOR) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

PURLIN

CS ROOF PANEL

PURLIN

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN * DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

1"

* INSIDE CLOSURE

TOP VIEW

GABLE EXTENSION CHANNEL (GEC) 1/4-14 X 7/8" (12" C.C.)

PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

EXTENSION FLASHING (EF)

#12-14 X 1" PANCAKE HEAD EACH PURLIN #12-14 X 1 1/4" (12" C.C.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

WALL PANEL

RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PURLIN CLOSURE INSTALLATION

STC-MSC Roof - Eave Extension

STC-MSC Roof Eave Extension

STC-MSC Low Side Eave Ext w Eave Gutter and CS-AP Soffit and Thermal Spacer

1/4-14 X 1 1/4" WT (8 PER PANEL)

** (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION (NOT BY CHIEF) PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)

BL

METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS

1/4-14 X 7/8" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) * TRAPEZOID PLUG (TRP) AT EACH HIGH RIB GUTTER STRAP (GSM) AT PANEL HI-RIBS #12-14 X 1 1/4" (TRIM COLOR)

STC/MSC ROOF PANEL

1/4-14 X 1 1/4" WT (6 PER PANEL)

EAVE GUTTER (EGM)

INTERMED. PURLIN ****

EAVE EXTENSION FLASHING (EEFA)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.) WALL PANEL OUTSIDE CLOSURE INSIDE CLOSURE *** #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 14" (12" C.C.) (TRIM COLOR) 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) SOFFIT PANEL 1/4-14 X 1" (2 PER CLOSURE)

EXTENSION FLASHING (EF)

PANEL OVERHANG

GUTTER STRAP LAP

PITCH

1/4-14 X 7/8" (12" C.C.)

<=3/4:12 >3/4:12 to <=1 1/2:12 >1 1/2:12 to <=2 1/2:12 >2 1/2:12 to <=3 1/2:12 >3 1/2:12 to <=4 1/2:12 ALL DIMENSIONS IN INCHES 4 1/2 3 1/2 3 1/2 4 4 1/4

7 7/8 7 1/2

OUTSIDE CLOSURE

7 1/8

6 7/16

5 3/4

DRAFTING NOTES: ***

** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. * See isometric Trapezoid Plug Installation detail for installation instructions.

Inside closure must be provided on buildings with liner insulation system. **** If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer.

Made with FlippingBook flipbook maker